Pacific Northwest – vapor barriers with spray foam?

Table of Contents

Home Community Forum Regional Chapters Pacific Northwest – vapor barriers with spray foam?

  • This topic is empty.
Viewing 5 posts - 1 through 5 (of 5 total)
  • Author
    Posts
  • #2789

    Working in Oregon and Washington. Getting conflicting info on whether we need a separate vapor barrier when using closed cell foam on exterior walls. Anyone doing work in the PNW have clarity on this?

    #2791

    In the PNW you are in climate zone 4C marine. Closed cell foam at 2 inches plus already functions as a vapor retarder Class II. Most code interpretations do not require an additional vapor barrier with sufficient closed cell.

    #2792
    Amy Chambers
    Member

    Washington state has adopted specific amendments to the IECC. Most of WA west of the Cascades is zone 4C or 4A. Worth a call to the building department before the job.

    #2794

    Called my local AHJ – they confirmed no additional vapor barrier needed with 2 inch minimum closed cell on exterior walls. Thanks for pointing me in the right direction!

    #2795
    Lars Eriksen
    Member

    Good info. In Minnesota we are in zone 6-7 and the rules are different but the principle of getting local AHJ clarification applies everywhere.

Viewing 5 posts - 1 through 5 (of 5 total)
  • You must be logged in to reply to this topic.

Uncategorized

Uncategorized

Uncategorized

REVIEWS YOU CAN RELY ON

Our Network

Spray foam insulation can crank up the performance of your homes—if you do it right. Check out our daily posts on the Foam Insulation and the Foam Insulation Market. We review each company and relay the information directly to you. Join our mailing list and have them sent directly to your email each and every day.
If you would like to know more about polyurea or spray foam, we recommend visiting ArmorThane
Mike T. (TX) posted in Contractor Talk: "Best temp settings for 2lb foam in summer heat"New article: "Spray Foam R-Value: The Complete Guide" — Read it nowSarah K. (OH) rated a contractor 5 stars in ClevelandWebinar: Cold Climate Installations — June 18 at 2PM EDT — Register Free28 new members joined this week!Texas Chapter Meetup: June 24 in Dallas — RSVP nowFoamPro_Dave replied: "Graco vs Gusmer after 8 years — my verdict"Mike T. (TX) posted in Contractor Talk: "Best temp settings for 2lb foam in summer heat"New article: "Spray Foam R-Value: The Complete Guide" — Read it nowSarah K. (OH) rated a contractor 5 stars in ClevelandWebinar: Cold Climate Installations — June 18 at 2PM EDT — Register Free28 new members joined this week!Texas Chapter Meetup: June 24 in Dallas — RSVP nowFoamPro_Dave replied: "Graco vs Gusmer after 8 years — my verdict"
👥 14,247 Members💬 312 Active This Week📰 131 Articles4.9/5 Rating📅 4 Events This Month
LIVE Community
Mike T. (TX) posted in Contractor Talk
2 min ago
Sarah K. (OH) asked in Ask An Expert
9 min ago
FoamPro_Dave replied in Equipment and Rigs
15 min ago
NewContractor2025 joined the community
32 min ago
Linda G. (OR) posted in Green Building
48 min ago
Join 14,247 Members Free